Short answer: A TM44 inspection is the legal energy inspection for air conditioning in buildings. If the systems in a building have an effective rated output of more than 12kW, an accredited energy assessor must inspect them at least every five years. It is separate from servicing and from F-gas leak checks, which have their own rules.
What TM44 is
TM44 is the name of the guidance used by energy assessors to inspect air conditioning systems in buildings. The legal duty comes from the Energy Performance of Buildings regulations. The government’s guide to air conditioning inspections says that all air conditioning systems with an effective rated output of more than 12kW must be regularly inspected by an energy assessor.
In practice, “TM44 inspection” is what building managers, landlords and agents call it.
The 12kW threshold
The 12kW figure refers to the effective rated output of the air conditioning in the building, and multiple systems can count together. A single wall unit in a small office will be well below it. A floor of ceiling cassettes on a multi zone system, or several split systems serving one building, can easily pass it.
| Situation | Likely over 12kW? |
|---|---|
| One wall unit in a small studio | no |
| Two or three small splits in a shop | possibly, check the ratings |
| Open plan office floor with cassettes | often yes |
| Multi let office building with central plant | yes |
| Server room with dedicated units plus office cooling | often yes |
If you are not sure, the rated outputs are on each unit’s data plate and in the installation paperwork. An energy assessor can confirm.
How often, and by whom
The inspection must be carried out at least every five years by an accredited air conditioning energy assessor. The report is lodged on the national register. Keep a copy with the building’s records: managing agents, buyers and tenants may ask for it.
What the inspector looks at
A TM44 inspection is about energy use and suitability, not cleaning. Typically the assessor will:
- review the system’s records, maintenance logs and any previous report
- look at the size of the system against the cooling load of the building
- check the condition and efficiency of the main components
- review controls, time settings and set points
- look at how the building is used and whether cooling is needed where it is supplied
- give advice on improvements, such as better controls, replacing old plant or reducing loads
The aim is to cut wasted energy. A common finding in London offices is cooling and heating running at the same time in different zones, or systems running overnight and at weekends when the building is empty.
How it fits with other duties
TM44 sits alongside two other things:
| Duty | What it is | Frequency |
|---|---|---|
| TM44 inspection | energy and suitability inspection by an energy assessor | at least every 5 years for systems over 12kW |
| F-gas leak checks | legal checks for refrigerant leaks by a certified engineer | set by the charge size, for systems at or above 5 tonnes CO2 equivalent (gov.uk) |
| Servicing | cleaning and maintenance | usually at least yearly, as the manufacturer advises |
Servicing and F-gas leak checks are carried out by an engineer with an F-gas qualification working for a certified company. TM44 is done by an energy assessor, who may or may not also be a refrigeration engineer.
Canary Wharf and other managed estates
Many offices at Canary Wharf, on the Isle of Dogs and across Tower Hamlets sit in large managed buildings where the landlord runs central plant and tenants add their own cooling for meeting rooms or comms rooms. In that set up:
- the landlord or estate usually holds the TM44 for the base building systems
- a tenant who installs its own systems may be responsible for those
- the lease and the building manager will set out who does what
If you are a tenant planning new cooling, ask the building manager whether your new units will be added to the building’s TM44 records or whether you need your own inspection. Our Canary Wharf area page covers the local set up, and our guide to office air conditioning and landlord consent explains the approvals.
Getting ready for an inspection
Before the assessor visits, gather:
- a list of all air conditioning units in the building, with makes, models and rated outputs
- installation and commissioning records
- maintenance and service records
- F-gas leak check records
- any previous TM44 report
- a plan showing which areas each system serves
Having these ready saves time on site and gives a more useful report.
Acting on the report
A TM44 report is advice rather than a list of compulsory works, but it often points to quick wins: setting timers correctly, stopping heating and cooling fighting each other, cleaning coils, or replacing very old, inefficient units. If replacement makes sense, plan it alongside your lease position and the landlord’s consent process. Our office air conditioning page explains how we survey and design commercial systems.
Quick questions
Who needs a TM44 inspection?
The person who controls the operation of air conditioning systems in a building, where the systems have an effective rated output of more than 12kW. That is often the landlord or building manager in a multi let office, or the occupier in a single let building.
How often is a TM44 inspection needed?
At least every five years, according to the government's guide to air conditioning inspections.
Is a TM44 inspection the same as a service?
No. A TM44 inspection assesses the system's efficiency and sizing and gives advice. A service cleans and maintains the equipment. F-gas leak checks are a third, separate legal requirement.
Last updated 23 October 2026. Written for homes in London. Rules can change, so check the linked sources for the latest position.